NEMO|etc.
Certificate of Authorization #32455
353 Christian Street, Unit #13
Oxford, CT 06478
(203) 262-9245
ENGINEER
EVALUATE
TEST
CONSULT
EVALUATION REPORT BY FLORIDA P.E.
GAF
1 Campus Drive
Parsippany, NJ 07054
(800) 766-3411
Evaluation Report 01506.04.08-R26
FL10626-R26 (NON-HVHZ)
Date of Issuance: 04/25/2008
Revision 26: 02/06/2023
DESCRIPTION: GAF Roof Underlayments for use in FBC non-HVHZ jurisdictions
This Evaluation Report consists of pages 1 through 10.
Prepared by:
©2019 NEMO ETC, LLC
Digitally signed
by Robert
Nieminen
Date: 2023.02.06
'15:57:35 -05'00
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 2 of 10
ROOFING COMPONENT EVALUATION:
1.
SCOPE:
Product Category: Roofing
Sub-Category: Underlayment
Product Approval Method: Method 1, Option D Codified Material, Evaluation by Engineer
Compliance Statement: GAF Roof Underlayments, as produced by GAF, have demonstrated compliance with the
following sections of the 7
th
Edition (2020) Florida Building Code through testing in accordance with the following
Standards. Compliance is subject to the Installation Requirements and Limitations of Use set forth herein.
2.
STANDARDS:
SECTION
PROPERTY
STANDARD
YEAR
1504.3.1
Wind resistance
FM 4474
2011
1504.7
Impact resistance
ASTM D3746
2015
1507.1.1, 1507.2.4, 1507.2.9.2 / R905.1.1,
R905.2.8.2
Material standard
ASTM D1970
2015
1507.1.1.1(2&3, Exception), 1507.1.1.1(5) /
R905.1.1.1(2&3, Exception), R905.1.1.1(5)
Tear Strength
ASTM D4533
2015
1507.1.1.1(2&3, Exception), 1507.1.1.1(5) /
R905.1.1.1(2&3, Exception), R905.1.1.1(5)
Tensile strength
ASTM D5035
2011
1507.1.1.1(5) / R905.1.1.1(5)
Liquid water transmission
ASTM D4869
2016
1507.1.1 / R905.1.1
Material standard
ASTM D6757
2016
1507.3.3, R905.3.3
Material standard
FRSA/TRI, Sixth Edition
2018
1507.11.2
Material standard
ASTM D6164
2011
TAS 110
Accelerated Weathering
ASTM D4798
2011
3.
REFERENCES:
ENTITY
EXAMINATION
REFERENCE
DATE
ERD (TST6049)
ASTM D6164 (GA)
G40630.01.14-2B-R2
01/07/14
ERD (TST6049)
ASTM D6164 (GA)
G46160.09.14-3A
09/09/14
ERD (TST6049)
ASTM D1970 (GA)
GAF-SC13285.03.17-3
03/01/17
ERD (TST6049)
ASTM D1970 (GA)
GAF-SC13285.03.17-4
03/01/17
ERD (TST6049)
ASTM D1970 (GA)
GAF-SC13285.03.17-1
03/08/17
ERD (TST6049)
ASTM D1970 (IN)
GAF-SC16440.12.17
12/31/17
Intertek (TST1558)
ASTM D4869 (Dadra, India)
F8549.02-106-18
11/08/16
NEMO (TST6049)
Physical Properties (ON)
4q-GAF-19-SSMBB-03.A
05/13/19
NEMO (TST6049)
ASTM D1623
4p-DOW-19-SSLAP-01.A-R2
10/01/19
NEMO (TST6049)
ASTM D1970
4j-FTS-20-SSUDL-01.A
12/01/20
NEMO (TST6049)
ASTM D1970
4j-GAF-20-SSUDL-01.A
12/22/20
NEMO (TST6049)
ASTM D4798, TAS 103
4j-GAF-20-SSUDL-02.A
03/15/21
NEMO (TST6049)
ASTM D4798
4j-FTS-21-SSUDL-02.A
06/09/21
NEMO (TST6049)
ASTM D4798, ASTM D3746
4j-GAF-21-SSUDL-02.A
11/19/21
NEMO (TST6049)
ASTM D1623 & FRSA/TRI (Slippage)
4j-GAF-22-SSUDL-01.A
08/09/22
NEMO (TST6049)
ASTM D1970, D4798
4j-GAF-22-SSUDL-02.A
08/29/22
NEMO (TST6049)
ASTM D1970, D4798
4j-GAF-22-SSUDL-05.A
01/03/23
NEMO (TST6049)
ASTM D226 (OK), Service Confirm
4j-GAF-23-SSUDL-01
01/26/23
PRI (TST5878)
Wind Uplift
GAF-434-02-01
09/16/13
PRI (TST5878)
Wind Uplift
GAF-434-02-03
09/16/13
PRI (TST5878)
Wind Uplift
GAF-434-02-04
09/16/13
PRI (TST5878)
ASTM D4533 (various)
GAF-818-02-01
12/05/17
PRI (TST5878)
ASTM D1970 (AL)
MSA-047-02-01
04/11/18
PRI (TST5878)
ASTM D4533 (Dadra, India)
GAF-847-02-01
06/04/18
PRI (TST5878)
ASTM D4533 (Dadra, India)
GAF-914-02-01
04/10/19
PRI (TST5878)
ASTM D4533, D5035 (VA)
376T0012
07/15/19
PRI (TST5878)
ASTM D4533 (Parzai, India)
376T0018
07/31/19
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 3 of 10
ENTITY
EXAMINATION
REFERENCE
DATE
PRI (TST5878)
ASTM D4533 (Umerkui Kilvani, India)
376T0018
07/31/19
PRI (TST5878)
ASTM D1970 (AR)
376T0032
10/22/19
PRI (TST5878)
ASTM D4533 (Gujarat, India)
376T0058
02/18/20
PRI (TST5878)
ASTM D226 (S-CA)
376T0054
02/18/20
PRI (TST5878)
ASTM D5035 (various)
376T0103
09/11/20
PRI (TST5878)
ASTM D4533, D5035 (Rajasthan, India)
376T0111
12/22/20
PRI (TST5878)
ASTM D4533, D5035 (Gujarat, India)
376T0113
12/22/20
PRI (TST5878)
ASTM D5035 (Gujarat, India)
376T0146
03/11/21
PRI (TST5878)
ASTM D4533, D5035 (Rajasthan, India)
376T0161
05/07/21
PRI (TST5878)
ASTM D226, Type II
376T0192
09/16/21
PRI (TST5878)
TAS 114(C)
376T0310
07/19/22
PRI (TST5878)
ASTM D1970 (IN)
376T0342
12/05/22
NEMO
Traceability
FBC Cross-Listing
04/22/20
NEMO
Traceability
FBC Cross-Listing
04/08/21
UL, LLC (QUA9625)
Quality Control
Service Confirmation (AL)
05/04/20
UL, LLC (QUA9625)
Quality Control
Service Confirmation (various)
07/12/22
UL, LLC (QUA9625)
Quality Control
Florida BCIS
Current
4.
PRODUCT DESCRIPTION:
TABLE 1: EVALUATED UNDERLAYMENTS
PRODUCT
MATERIAL STANDARD
PLANT(S)
GAF Extended Dry-In Membrane
ASTM D1970 and FRSA/TRI 09-18
Langley, BC Canada
LIBERTY SBS Self-Adhering Base/Ply
Sheet
ASTM D1970
Mt. Vernon, IN
Savannah, GA
StormGuard® Film-Surfaced Leak Barrier
ASTM D1970 (Table 1)
1
Mt. Vernon, IN
Savannah, GA
WeatherWatch® Mineral-Surfaced Leak
Barrier
ASTM D1970
Arkadelphia, AR
Mt. Vernon, IN
Savannah, GA
Stockton, CA
Tuscaloosa, AL
Deck-Armor Premium Breathable Roof
Deck Protection
1507.1.1.1(2&3, Exception) /
R905.1.1.1(2&3, Exception)
Dadra, India
FeltBuster® Synthetic Roofing Felt
1507.1.1.1(2&3, Exception), 1507.1.1.1(5) /
R905.1.1.1(2&3, Exception), R905.1.1.1(5)
Dadra, India
Gujarat, India
(CPP) Rajasthan, India
(MIP) Rajasthan, India
Richmond, VA
Spartanburg, SC
Shingle-Mate® Roof Deck Protection
ASTM D226, Type II (Table 1)
Pryor, OK
Shafter, CA
StormSafe Anchor Sheet
1507.1.1.1(2&3, Exception) /
R905.1.1.1(2&3, Exception)
North Bay, ON
Tiger Paw Premium Roof Deck
Protection
1507.1.1.1(2&3, Exception) /
R905.1.1.1(2&3, Exception)
Dadra, India
Gujarat, India
Parzai, India
Umerkui Kilvani, India
1
StormGuard® Film-Surfaced Leak Barrier has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt
when tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth in Section 4.3, Note 1 of ASTM D1970-15, should be
established as to slip resistance.
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 4 of 10
TABLE 1: EVALUATED UNDERLAYMENTS
PRODUCT
MATERIAL STANDARD
PLANT(S)
VersaShield® Fire-Resistant Roof Deck
Protection
ASTM D226, Type II
Conover, NC
Ruberoid® Mop Granule
ASTM D6164
FRSA/TRI 09-18
Savannah, GA
Ruberoid® Mop Granule FR
ASTM D6164
FRSA/TRI 09-18
Savannah, GA
5.
LIMITATIONS:
5.1
This is a building code evaluation. Neither NEMO ETC, LLC nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting
or design guidance unless retained specifically for that purpose.
5.2
This Evaluation Report is not for use in FBC High Velocity Hurricane Zone jurisdictions (i.e., Broward and Miami-
Dade Counties).
5.3
This Evaluation Report pertains to above-deck roof components. Roof decks and structural members shall be in
accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
5.4
This Evaluation Report does not include evaluation of fire classification. Refer to FBC 1505 for requirements and
limitations regarding roof assembly fire classification. Refer to FBC 2603 for requirements and limitations
concerning the use of foam plastic insulation.
5.5
GAF Roof Underlayments may be used with any prepared roof cover where the product is specifically referenced
within FBC approval documents. If not listed, a request may be made to the Authority Having Jurisdiction for
approval based on this evaluation combined with supporting data for the prepared roof covering.
5.6
Allowable Roof Covers:
TABLE 2: ROOF COVER OPTIONS
FBC NON-HVHZ:
1507.2
1507.3
1507.4 & 1507.5
1507.7
1507.8 & 1507.9
UNDERLAYMENT
ASPHALT
SHINGLES
CLAY AND CONCRETE TILE
METAL
SLATE OR
SLATE-TYPE
SHINGLES
WOOD
MECHANICAL
ATTACH
ADHESIVE-
SET
PANELS
SHINGLES
SHINGLES
SHAKES
GAF Extended Dry-In Membrane
Yes
Yes
No
Yes
Yes
Yes
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
LIBERTY SBS Self-Adhering
Base/Ply Sheet
Yes
No
No
No
No
No
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
StormGuard® Film-Surfaced Leak
Barrier
Yes
No
No
Yes
Yes
Yes
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
WeatherWatch® Mineral-Surfaced
Leak Barrier
Yes
No
No
No
No
No
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
Yes
(joint strips,
1507.1.1.3 /
R905.1.1.3)
Deck-Armor Premium Breathable
Roof Deck Protection
Yes
No
No
Yes
Yes
Yes
No
No
FeltBuster® Synthetic Roofing Felt
Yes
No
No
No
No
No
No
No
Shingle-Mate® Roof Deck
Protection
Yes
No
No
No
No
No
No
No
Tiger Paw Premium Roof Deck
Protection
Yes
No
No
Yes
Yes
Yes
No
No
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 5 of 10
TABLE 2: ROOF COVER OPTIONS
FBC NON-HVHZ:
1507.2
1507.3
1507.4 & 1507.5
1507.7
1507.8 & 1507.9
UNDERLAYMENT
ASPHALT
SHINGLES
CLAY AND CONCRETE TILE
METAL
SLATE OR
SLATE-TYPE
SHINGLES
WOOD
MECHANICAL
ATTACH
ADHESIVE-
SET
PANELS
SHINGLES
SHINGLES
SHAKES
VersaShield® Fire-Resistant Roof
Deck Protection
Yes
No
No
No
No
No
No
No
Ruberoid® Mop Granule
No
Yes
(Cap Sheet in
2-ply system)
Yes
(Cap Sheet in
2-ply system)
(Table 2A)
No
No
No
No
No
Ruberoid® Mop Granule FR
No
Yes
(Cap Sheet in
2-ply system)
Yes
(Cap Sheet in
2-ply system)
(Table 2A)
No
No
No
No
No
5.6.1
Adhesive-set is limited to use of following underlayment / tile-adhesive combinations.
TABLE 2A: ALLOWABLE UNDERLAYMENT / TILE-ADHESIVE COMBINATIONS
2
UNDERLAYMENT
ADHESIVE
FBC
Ruberoid® Mop Granule;
Ruberoid® Mop Granule FR
DAP Global “Touch ‘n Seal® Storm Bond® Low GWP Adhesive”
FL14506
DAP Global “Touch ‘n Seal® Storm Bond® 2 Roof Tile Adhesive
Low GWP”
FL14506
Dupont de Nemours “Tile Bond™ Roof Tile Adhesive”
FL22525
ICP Construction “Polyset® AH-160”
FL6332
ICP Construction “APOC Polyset® RTA-1”
FL6276
5.7
Allowable Substrates:
TABLE 3: SUBSTRATE OPTIONS FOR ADHERED UNDERLAYMENTS
UNDERLAYMENT
APPLICATION
PRIMER
SUBSTRATES
GAF Extended Dry-In Membrane
self-adhering
None
plywood
LIBERTY SBS Self-Adhering Base/Ply Sheet
self-adhering
(Optional)
ASTM D41
plywood
StormGuard® Film-Surfaced Leak Barrier
Weather Watch® Mineral-Surfaced Leak Barrier
LIBERTY SBS Self-Adhering Base/Ply Sheet
self-adhering
None
ASTM D226 felt, Type II
StormGuard® Film-Surfaced Leak Barrier
Weather Watch® Mineral-Surfaced Leak Barrier
LIBERTY SBS Self-Adhering Base/Ply Sheet
self-adhering
ASTM D41
metal (flashing metal, valley metal,
etc.)
StormGuard® Film-Surfaced Leak Barrier
Weather Watch® Mineral-Surfaced Leak Barrier
Ruberoid® Mop Granule
hot asphalt
ASTM D41
structural concrete
Ruberoid® Mop Granule FR
Ruberoid® Mop Granule
hot asphalt
None
ASTM D226, Type II felt, GAFGLAS®
#80 Ultima Base Sheet or
Ruberoid® 20 Smooth
Ruberoid® Mop Granule FR
2
Refer to Tile Manufacturer’s or Adhesive Manufacturer’s Florida Product Approval for Overturning Moment Resistance Performance.
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 6 of 10
5.8
Attachment Limitations:
5.8.1
For use under mechanically attached NON-TILE prepared roof coverings, attachment shall be in accordance with
the manufacturer’s installation instructions, but – for mechanically attached underlayments or base sheets - not
less than FBC 1507.1.1 or R905.1.1.
5.8.2
For use under tile roof systems, attachment shall be in accordance with the manufacturer’s installation
instructions, but for mechanically attached base sheets - not less than:
FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A,
Table 1 (for Two-Ply Asphalt Applied Hot Mop Underlayment)
or
Table 4A or Table 4B herein (for other underlayment systems).
5.8.3
Wind Resistance for Underlayment Systems in Tile Roof Applications:
The following wind uplift limitations apply to underlayment systems that are not prescriptive in the FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition. The Maximum Design Pressure
is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing
pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied).
5.8.3.1
Direct-to-Deck:
The maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A, Table 1A or the
critical (highest) design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3.
TABLE 4A: ALLOWABLE DESIGN PRESSURES,
DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
SYSTEM
NO.
DECK
BASE PLY
CAP PLY
DESIGN
PRESSURE
(PSF)
1
Min. 15/32-
inch PS 1-09,
CDX plywood
None
GAF Extended Dry-In Membrane, self-adhered
and back-nailed within the selvedge-edge side
laps using corrosion resistant 12 ga. x 1¼” ring
shank nails through 32 ga., 1-5/8” diameter tin
caps or corrosion resistant 1-inch diameter
metal cap nails, max. 12-inch o.c.
-45.0
2
Min. 2,500 psi
structural
concrete
GAFGLAS #75 Base Sheet, Tri-Ply #75
Base Sheet, GAFGLAS #80 Ultima Base
Sheet, GAFGLAS Ply 4, Tri-Ply Ply 4 or
GAFGLAS Flex Ply 6 applied in full
mopping of ASTM D312, Type IV hot
asphalt at 20 to 25 lbs/square
Ruberoid® Mop Granule or Ruberoid® Mop
Granule FR applied in full mopping of ASTM
D312, Type IV hot asphalt at 20 to 25
lbs/square, and back-nailed in accordance with
GAF installation instructions, max. 12-inch o.c.
-442.5
5.8.3.2
Mechanically-Attached Base Sheet:
The maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI
Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition, Appendix A, Table 1A or the
critical (highest) design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3.
Alternatively, the maximum design pressure for the selected assembly shall meet or exceed at least the Zone 1
design pressure determined in accordance with FBC 1609 or FBC Residential Chapter 3. Elevated pressure zones
shall employ an attachment density designed by a qualified design professional to resist the elevated pressure
criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing
Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section
2.2.10.1 of FM Loss Prevention Data Sheet 1-29 for enhancements.
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 7 of 10
TABLE 4B: ALLOWABLE DESIGN PRESSURES,
2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF APPLICATIONS
SYSTEM
NO.
DECK
BASE SHEET
CAP PLY
DESIGN
PRESSURE
(PSF)
3
Min. 19/32-
inch plywood
GAFGLAS® #80 Ultima Base Sheet or Ruberoid®
20 Smooth mechanically attached with 12 ga.,
min. 1.25-inch long ring shank nails through 32
ga., 1-5/8-inch diameter tin caps spaced 9-inch
o.c. at the min. 4-inch wide side laps and 9-inch
o.c. at two (2), equally spaced, staggered center
rows in the field of the sheet
Ruberoid® Mop Granule or
Ruberoid® Mop Granule FR applied
in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25
lbs/square, and back-nailed in
accordance with GAF installation
instructions, max. 12-inch o.c.
-45.0
4
Min. 19/32-
inch plywood
GAFGLAS® #80 Ultima Base Sheet or Ruberoid®
20 Smooth mechanically attached with 12 ga.,
min. 1.25-inch long ring shank nails through 32
ga., 1-5/8-inch diameter tin caps spaced 8-inch
o.c. at the min. 4-inch wide side laps and 8-inch
o.c. at three (3), equally spaced, staggered center
rows in the field of the sheet
Ruberoid® Mop Granule or
Ruberoid® Mop Granule FR applied
in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25
lbs/square, and back-nailed in
accordance with GAF installation
instructions, max. 12-inch o.c.
-75.0
5
Min. 19/32-
inch plywood
GAFGLAS® #80 Ultima Base Sheet or Ruberoid®
20 Smooth mechanically attached with 11 ga.,
min. 1.25-inch long ring shank nails through 32
ga., 1-5/8-inch diameter tin caps spaced 4-inch
o.c. at the min. 2-inch wide side laps and 4-inch
o.c. at four (4), equally spaced center rows in the
field of the sheet
Ruberoid® Mop Granule or
Ruberoid® Mop Granule FR applied
in full mopping of ASTM D312, Type
IV hot asphalt at 20 to 25
lbs/square, and back-nailed in
accordance with GAF installation
instructions, max. 12-inch o.c.
-97.5
5.9
Exposure Limitations:
TABLE 5: EXPOSURE LIMITATIONS
UNDERLAYMENT
PREPARED ROOF COVER
INSTALLATION TYPE
MAXIMUM
EXPOSURE
(DAYS)
Deck-Armor Premium Breathable Roof Deck Protection, FeltBuster® Synthetic
Roofing Felt, Shingle-Mate® Roof Deck Protection, StormSafe Anchor Sheet,
Tiger Paw Premium Roof Deck Protection, VersaShield® Fire-Resistant Roof
Deck Protection and LIBERTY SBS Self-Adhering Base/Ply Sheet
Mechanically attached
30
WeatherWatch® Mineral-Surfaced Leak Barrier
Mechanically attached
60
StormGuard® Film-Surfaced Leak Barrier
Mechanically attached
90
GAF Extended Dry-In Membrane
Mechanically attached
360
Ruberoid® Mop Granule and Ruberoid® Mop Granule FR
Adhesive-set tile roof system
180
Mechanically attached
UNLIMITED
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 8 of 10
5.10
Tile Slippage Limitations:
When loading roof tiles on the underlayment in direct-deck tile roof assemblies, the maximum roof slope shall be
as follows. Slopes in excess of these limitations require the use of battens or loading boards during loading of the
roof tiles, in which case the maximum staging method is a 10-tile stack.
TABLE 6: TILE SLIPPAGE LIMITATIONS FOR DIRECT-DECK TILE INSTALLATIONS
UNDERLAYMENT
TILE PROFILE
STAGING METHOD
MAXIMUM STAGING SLOPE
GAF Extended Dry-In Membrane
Flat or Lugged
10-tile stack
4:12
Flat or Lugged
6-tile stack (4 over 2)
7:12
Ruberoid® Mop Granule
Flat
Max. 10-tile stack
4:12
Lugged
battens or loading-boards required
N/A
Ruberoid® Mop Granule FR
Flat or Lugged
battens or loading-boards required
N/A
5.11
All components in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20-3.
Refer to the Product Approval of the component manufacturer for components mentioned herein that are
produced by a Product Manufacturer other than the report holder on Page 1 of this Evaluation Report.
6.
INSTALLATION:
6.1
GAF Roof Underlayments shall be installed in accordance with GAF published installation instructions subject to
the Limitations of Use set forth herein and the specifics noted below.
6.1.1
Consult GAF requirements for back-nailing at slopes 2:12 or greater.
6.2
Re-fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to
remove any dust and debris prior to application and prime the substrate (if applicable).
6.3
Deck-Armor Premium Breathable Roof Deck Protection or Tiger Paw Premium Roof Deck Protection:
6.3.1
Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1.1.1(2, Exception)
or 1507.1.1.1(3, Exception) or FBC Residential R905.1.1.1(2, Exception) or R905.1.1.1(3, Exception) for the type
of prepared roof covering to be installed, and the manufacturer’s installation instructions. FBC requirements take
precedence over the manufacturer’s installation instructions.
6.4
FeltBuster® Synthetic Roofing Felt:
6.4.1
Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1.1.1(2, Exception),
1507.1.1.1(3, Exception) or 1507.1.1.1(5) or FBC Residential R905.1.1.1(2, Exception), R905.1.1.1(3, Exception)
or R905.1.1.1(5) for the type of prepared roof covering to be installed, and the manufacturer’s installation
instructions. FBC requirements take precedence over the manufacturer’s installation instructions.
6.5
StormSafe Anchor Sheet:
6.5.1
StormSafe Anchor Sheet is limited to use as a mechanically attached base layer in 2-ply underlayment systems.
6.5.2
Shall be installed in compliance with requirements for a synthetic underlayment in FBC 1507.1.1.1(2, Exception)
or 1507.1.1.1(3, Exception) or FBC Residential R905.1.1.1(2, Exception) or R905.1.1.1(3, Exception) for the type
of prepared roof covering to be installed, and the manufacturer’s installation instructions. FBC requirements take
precedence over the manufacturer’s installation instructions.
6.5.3
One the same day, install LIBERTY SBS Self-Adhering Base/Ply; StormGuard® Film-Surfaced Leak Barrier or
WeatherWatch® Mineral-Surfaced Leak Barrier over the StormSafe Anchor Sheet.
6.6
Shingle-Mate® Roof Deck Protection:
6.6.1
Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM
D226, Type II) in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering
to be installed, and the manufacturer’s installation instructions. FBC requirements take precedence over the
manufacturer’s installation instructions.
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 9 of 10
6.7
VersaShield® Fire-Resistant Roof Deck Protection:
6.7.1
Shall be installed in compliance with requirements for an approved mechanically attached underlayment (ASTM
D6757) in FBC Table 1507.1.1.1 or FBC Residential Table R905.1.1.1 for the type of prepared roof covering to be
installed, and the manufacturer’s installation instructions. FBC requirements take precedence over the
manufacturer’s installation instructions.
6.8
LIBERTY SBS Self-Adhering Base/Ply Sheet, StormGuard® Film-Surfaced Leak Barrier or WeatherWatch®
Mineral-Surfaced Leak Barrier:
6.8.1
Shall be installed in compliance with requirements for an approved self-adhering underlayment (ASTM D1970)
in FBC 1507.1.1.1 or 1507.1.1.3 or FBC Residential R905.1.1.1 or R905.1.1.3 for the type of prepared roof
covering to be installed, and the manufacturer’s installation instructions.
6.8.2
Back-nailing is required. Back-nailing shall consist of Approved cap nails spaced max. 18-inch o.c., encapsulated
within min. 4-inch side laps.
6.8.3
When installed over a mechanically attached, FBC Approved ASTM D226 Type II felt, the felt shall be fastened in
accordance with FBC 1507.1.1 or R905.1.1.
6.8.4
LIBERTY SBS Self-Adhering Base/Ply Sheet, StormGuard® Film-Surfaced Leak Barrier or WeatherWatch®
Mineral-Surfaced Leak Barrier may be installed as a secondary water barrier using minimum 4-inch wide rolls to
seal plywood deck joints prior to installation of the primary underlayment system.
6.9
GAF Extended Dry-In Membrane:
6.9.1
Non-Tile Applications:
Shall be installed in compliance with requirements for an approved self-adhering underlayment (ASTM D1970)
in FBC 1507.1.1.1 or 1507.1.1.3 or FBC Residential R905.1.1.1 or R905.1.1.3 for the type of prepared roof
covering to be installed, and the manufacturer’s installation instructions.
Back-nailing is required. Back-nailing shall consist of Approved cap nails spaced max. 18-inch o.c., encapsulated
within min. 4-inch side laps.
6.9.2
Mechanically Attached Tile Applications:
Shall be installed in compliance with the requirements for Self-Adhered Membrane set forth in FRSA/TRI Florida
High Wind Concrete and Clay Roof Tile Installation Manual, Sixth Edition and the manufacturer’s installation
instructions.
Refer to Section 5.8 herein for attachment limitations.
Refer to Table 6 herein for tile staging limitations.
6.9.3
GAF Extended Dry-In Membrane may be installed as a secondary water barrier using minimum 4-inch wide rolls
to seal plywood deck joints prior to installation of the primary underlayment system.
6.10
Ruberoid® Mop Granule; Ruberoid® Mop Granule FR:
6.10.1
Shall be installed in compliance with requirements as an alternate to the Hot Asphalt Applied Cap Sheet in the
“Two Ply System” in the FRSA/TRI Florida High Wind Concrete and Clay Roof Tile Installation Manual, Sixth
Edition, and the manufacturer’s installation instructions.
6.10.2
Refer to Section 5.8 herein for attachment limitations.
6.10.3
Refer to Table 6 for tile staging limitations.
NEMO|etc.
NEMO ETC, LLC 7
TH
EDITION (2020) FBC NON-HVHZ EVALUATION (Method 1D) Evaluation Report 01506.04.08-R26
Certificate of Authorization #32455 GAF Roof Underlayments FL10626-R26 (NON-HVHZ)
BACK TO TOP Revision 26: 02/06/2023
Page 10 of 10
7.
BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction to properly evaluate the installation of this
product.
8.
MANUFACTURING PLANTS:
Contact the named QA entity for manufacturing facilities covered by F.A.C. Rule 61G20-3 QA requirements. Refer
to Section 4 herein for products and production locations having met codified material standards.
9.
QUALITY ASSURANCE ENTITY:
UL (QUA9625): (360) 817-5512; b[email protected]m
- END OF EVALUATION REPORT -